CalcOpenly
English

Electrical load and breaker size calculator

Breaker size for one circuit: total watts and amps from a list of appliances, with the NEC 125% continuous-load rule and NEC or IEC breaker ratings.

Drafted with AI writing toolsUpdated Checked examples: 5

Name, power in W, kW or A; add “continuous” for anything that runs 3 hours or more, and “x 2” for several of the same.
More options
1 for heaters and lamps; motors and some electronics run 0.8–0.95.
Try
Suggested breaker
A
Suggested breaker: 20 A
Whole number; Nearest, ties away from zero
Total load
1,770W
Current drawn
14.75A
Minimum breaker rating
17.88A
Continuous part
1,500W
Breaker loading
73.8%
Size the wire to the breaker, not the load, and follow local code; this is an estimate, not a design.

The circuit draws 14.75 A (1,770 W). Counting continuous loads at 125%, the breaker must be at least 17.88 A, so the next standard size is 20 A.

Share of the load

Space heater (continuous)1,500 WTV150 WLamp × 2120 W

Current as a share of a 20 A breaker

Up to 80%80–100%Overloaded73.8%Up to 80%
Loads Rows: 3
LoadWattsAmpsType
Space heater1,50012.5Continuous
TV1501.25Non-continuous
Lamp × 21201Non-continuous
How it's calculated S
  1. Total load

    P=1,500+150+120=1,770 WP = 1{,}500 + 150 + 120 = 1{,}770\ \text{W}
  2. Current

    I=1,770120×1=14.75 AI = \frac{1{,}770}{120 \times 1} = 14.75\ \text{A}
  3. Minimum breaker rating (NEC 2023 210.20(A))

    2.25+1.25×12.5=17.875 A2.25 + 1.25 \times 12.5 = 17.875\ \text{A}

    Continuous loads (3 hours or more) count at 125%, which keeps them at or under 80% of the breaker.

  4. Next standard size

    20 A≥17.875 A20\ \text{A} \ge 17.875\ \text{A}

    From the NEC 2023 240.6(A) standard ratings.

About the electrical load and breaker size calculator

Each load is converted to amps with I = P ÷ (V × power factor), or P ÷ (√3 × V × power factor) on a three-phase supply. Loads marked continuous, meaning they run for 3 hours or more, count at 125%, and the smallest standard breaker at or above the total is suggested (NEC 2023 210.20(A) and 240.6(A), or the IEC 60898-1 ratings).

The default circuit, a 1,500 W space heater running continuously plus a 150 W TV and two 60 W lamps on 120 V, draws 14.75 A. With the heater counted at 125% the breaker must be at least 17.875 A, so the suggestion is 20 A, loaded to 73.8%.

The wire must be sized to the breaker. Motors, feeders and whole-house service loads follow other NEC articles, so treat the result as a check on one branch circuit, not a design.

What size breaker do I need?

Convert each load to amps, count continuous loads (running 3 hours or more) at 125%, and pick the next standard rating at or above the total (NEC 2023 210.20(A) and 240.6(A)). A continuous 1,500 W heater plus a 150 W TV and two 60 W lamps on 120 V needs at least 17.875 A, so a 20 A breaker.

This sizes the protection for one branch circuit. Feeders, whole-house service loads and motor circuits follow other NEC articles, and the wire is then sized to the breaker.

How to convert watts to amps

On a single-phase supply, I = P ÷ (V × pf). On a balanced three-phase supply, I = P ÷ (√3 × V × pf), with V the line-to-line voltage. A 2,000 W kettle on 230 V draws 8.70 A; 11 kW on 400 V three-phase draws 15.88 A per line.

The power factor (pf) is 1 for resistive loads such as heaters; motors and some electronics run about 0.8 to 0.95. A lower factor means more current for the same power: 1,000 W at 120 V draws 8.33 A at pf 1 and 10.42 A at pf 0.8.

Worked example: heater, TV and lamps on 120 V

  1. Continuous part. 1,500 W ÷ 120 V = 12.5 A, counted at 125%: 15.625 A.
  2. Noncontinuous part. 150 W + 2 × 60 W = 270 W, or 2.25 A.
  3. Minimum rating. 15.625 + 2.25 = 17.875 A.
  4. Breaker. 15 A is too small, so the next standard rating is 20 A.

The circuit actually draws 14.75 A, which is 73.75% of the 20 A breaker. The 125% factor raises the minimum rating, not the current, so 17.875 ÷ 20 = 89.375% is not the breaker's loading.

The 125% rule and the 80% rule

They are the same rule: 1 ÷ 1.25 = 0.8. A continuous load may use at most 80% of a standard breaker, so a 20 A breaker can carry 16 A continuously, or 1,920 W at 120 V.

A minimum that lands exactly on a rating uses that rating: 16 A × 1.25 = 20 A, so the 1,920 W heater fits a 20 A breaker.

Apply 125% only to the continuous part. Multiplying every load by 1.25 overstates the minimum: in the example above it gives 18.4375 A instead of 17.875 A.

The exception is a breaker in an assembly listed for continuous operation at 100% of its rating, as Schneider Electric explains. Without that listing, use the 125% factor.

Standard breaker sizes

NEC 240.6(A) standard ratings run 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90 and 100 A, then continue in larger steps. IEC 60898-1 miniature circuit breakers (MCBs) come in 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A.

The 125% factor is an NEC rule, and IEC-based wiring rules may not require it. Unmarked, the 11 kW three-phase load draws 15.88 A and the next IEC rating is 16 A, loaded to 99%; marked continuous, it needs 19.85 A and a 20 A MCB.

Circuit examples

The kitchen row is a 2,000 W kettle, 1,200 W microwave and 800 W toaster on 230 V, none continuous, sized to IEC ratings. The exact twenty row is a 1,920 W continuous heater on 120 V.

The EV row is a 32 A charger on 240 V, charging continuously. The three-phase row is 11 kW on 400 V at pf 1, marked continuous and sized to IEC ratings.

ScenarioTotal wattsMinimum rating, ASuggested rating, A
Default1770.00000017.87500020.000000
Kitchen IEC4000.00000017.39130420.000000
Exact twenty amp rating1920.00000020.00000020.000000
EV charger7680.00000040.00000040.000000
Three phase11000.00000019.84641620.000000

NEC 625.41 sizes EV charger protection for continuous duty, so the 32 A charger needs 32 × 1.25 = 40 A. The default row is the worked example above.

Size the wire to the breaker

Under NEC 2023 240.4(D), copper conductors may be protected at no more than 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG. A 20 A circuit therefore needs at least 12 AWG copper.

Hot locations and bundled cables lower a conductor's ampacity, and long runs add voltage drop; either can call for a larger size. Check a long run with the wire gauge and voltage-drop calculator.

Load list format

  • One load per line: a name, then the power in W, kW or A, as in Kettle, 2000 W. A number with no unit is read as watts.
  • Repeat identical loads with Lamp, 60 W x 2 or 2 x Lamp, 60 W.
  • Add continuous (or cont) to anything that runs 3 hours or more.
  • A load in amps keeps its current and is converted to watts at the chosen voltage: 32 A at 240 V is 7,680 W.
  • One power factor covers the whole list, so give a motor with a different factor in amps from its nameplate.

Mistakes to avoid

  • Sizing to the running current. 14.75 A seems to fit a 15 A breaker, but that loads it to 98% with a heater running for hours. The 125% rule moves the circuit to 20 A.
  • Using output instead of input. Use the electrical input on the nameplate, not an air conditioner's cooling capacity or a motor's shaft power. The horsepower calculator converts units, but efficiency separates output from input.
  • Raising the breaker without the wire. A 20 A breaker on 14 AWG copper exceeds the 240.4(D) limit.
  • Mixing standards. NEC sizes on a 230 V or 400 V supply, or the 125% factor on an IEC installation, may not match local rules.

The EV charging calculator estimates charging time and cost, the solar panel calculator sizes a rooftop array, and the BTU calculator sizes an air conditioner for a room.

Worked examples

Space heater (continuous), TV and two lamps at 120 V

Loads on the circuit (one per line)
Space heater, 1500 W, continuous TV, 150 W Lamp, 60 W x 2
Voltage
120 V
Supply
Single-phase
Breaker sizes
US (NEC)
Total load
1,770 W
Current drawn
14.75 A
Minimum breaker rating
17.88 A
Suggested breaker
20 A

Checked against: Independent calculation

Kitchen appliances at 230 V, IEC breakers

Loads on the circuit (one per line)
Kettle, 2000 W Microwave, 1200 W Toaster, 800 W
Voltage
230 V
Supply
Single-phase
Breaker sizes
IEC (MCB)
Total load
4,000 W
Current drawn
17.39 A
Suggested breaker
20 A

Checked against: Hand calculation: 4000/230 = 17.39 A, no continuous loads → IEC 60898-1 20 A

Edge: 1920 W continuous needs exactly 20 A

Loads on the circuit (one per line)
Heater, 1920 W, continuous
Voltage
120 V
Supply
Single-phase
Breaker sizes
US (NEC)
Current drawn
16 A
Minimum breaker rating
20 A
Suggested breaker
20 A
Breaker loading
80%

Checked against: Hand calculation: 1920/120 = 16 A × 1.25 = 20 A, which a 20 A breaker satisfies (16 A is 80% of 20 A)

32 A EV charger on 240 V

Loads on the circuit (one per line)
EV charger, 32 A, continuous
Voltage
240 V
Supply
Single-phase
Breaker sizes
US (NEC)
Total load
7,680 W
Minimum breaker rating
40 A
Suggested breaker
40 A

Checked against: Independent calculation

Questions

What size breaker do I need?

Add the non-continuous amps and 125% of the continuous amps, then take the next standard rating up (NEC 2023 210.20(A) and 240.6(A); standard ratings include 15, 20, 25, 30, 35 and 40 A). A 1,500 W heater running 3 hours or more on 120 V is 12.5 A × 1.25 = 15.625 A; with a 150 W TV and two 60 W lamps (2.25 A) the circuit needs 17.875 A, so a 20 A breaker.

What is the 80% rule for circuit breakers?

It is the 125% continuous-load rule read the other way: a load that runs 3 hours or more may use at most 80% of a standard breaker's rating, because 1 ÷ 1.25 = 0.8 (NEC 2023 210.20(A)). A 20 A breaker can carry 16 A continuously, which is 1,920 W at 120 V. Breakers in assemblies listed for continuous operation at 100% of their rating are the exception.

How do you convert watts to amps?

Divide watts by volts, and by the power factor for motors and electronics: I = P ÷ (V × pf). On a three-phase supply divide by √3 × V × pf instead. A 2,000 W kettle on 230 V draws 8.7 A; an 11 kW load on a 400 V three-phase supply draws 11,000 ÷ (1.732 × 400) = 15.88 A per phase.

What wire size goes with a 15, 20 or 30 amp breaker?

Under NEC 2023 240.4(D), copper conductors may be protected at no more than 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG. A 20 A circuit therefore needs at least 12 AWG copper. Hot locations and bundled cables lower a conductor's ampacity, and long runs add voltage drop, either of which can call for a larger size.

What are the standard MCB sizes in the UK and Europe?

IEC 60898-1 lists rated currents of 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A. A kettle, microwave and toaster totalling 4,000 W on 230 V draw 17.4 A, so the next MCB rating is 20 A. The 125% continuous-load factor is an NEC rule; leave loads unmarked to size to the plain current.

About this calculator

I=PV⋅pf (or P3 V⋅pf),Ibreaker≥Inon-cont+1.25 IcontI = \frac{P}{V \cdot \text{pf}}\ \big(\text{or } \tfrac{P}{\sqrt{3}\,V \cdot \text{pf}}\big),\qquad I_{\text{breaker}} \ge I_{\text{non-cont}} + 1.25\, I_{\text{cont}}

Sources

  1. NFPA 70 (NEC) 2023, 210.20(A) — overcurrent device ≥ noncontinuous load + 125% of continuous load
  2. NFPA 70 (NEC) 2023, 240.6(A) — standard ampere ratings
  3. NFPA 70 (NEC) 2023, 240.4(D) — small conductors: 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A (copper)
  4. IEC 60898-1 — preferred rated currents for miniature circuit breakers

Checked against references

This calculator includes 5 worked examples with independently sourced answers. They run in the test suite, and you can run them here too.

Put this calculator on your site

Paste this where you want the calculator to appear. It is free to use, it stays in step with corrections made here, and the credit line below it links back so your readers can find the full version.

Height
Preview the embed

Keep the credit line. It is the only condition, and it is what keeps these calculators free.